High Temperature Bottle Type Water Cooling Tower

Product Details
Customization: Available
Cooling Method: Cross Flow
Ventilation Mode: Natural Ventilation
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
19
Year of Establishment
2001-08-15
Find Similar Products

Basic Info.

Model NO.
WY-40T
Material
FRP
Air Contact Form
Wet
Air Contact Way
Open
Tower Shape
Round
Noise Level
Low
Application Fields
Industrial
Certification
ISO, CE
Condition
New
Model Number
Standard Fpr Cooling Tower
Dimension(L*W*H)
950X950X1500mm
Voltage
110V 220V 380V 450V
Power(W)
0.55kw
Weight
200kg
Transport Package
Wooden Case
Specification
PPT
Trademark
Wanyuan
Origin
Wenzhou China
Production Capacity
5000

Product Description

High Temperature Bottle Type Water cooling power
Industrial cooling tower series for water chillers/Water Cooling Tower

--Water Cooling Tower With High standard bearing, with minimum noise;
--With High quality seal motor, compeletely water proof from exterior;
--Easy for installations;
--No need to maintain oil and with low power consumption Water Cooling Tower;
--With well performance pump, optional for model suiting for high temperature conditions.

Water Towers - Buy Water Towers, Water Cooling Tower, Industrial Cooling Tower, standard FPR cooling tower

1. Cooling capacity ranges from 3 to 780 M3/h, relevant refrigeration ton is from 5 to1000.
2. Body: FRP body which contain stabilization material resisting ultraviolet radiation. It has long service life.
3. Fan: Use special fan with variable section, twist and pitching blade. The fan
Works at an equal speed, a low self moving pressure, an energy-saving use and a low noise. Fixing angle of blade is changeable to meet the work demands and improve the efficiency.
4. Motor: Choose special electric motor with whole sealed cooling tower, we use 380V/3φ /50Hz mostly.
5. Fill: With round counterflow model fill, be able to be extended the time and space of heat exchange.
6. Distribution: With rotating pipe model, the equipment is made of FRP
7. Structure: All structure be treated with rust-removing, hot dipped galvanized
Steel. All can bear corrosion, have high strength, be easily assembled and have
Elegant surface.
8. Type: Standard, low noise and High temperature, industrial type to meet customer's needs

Below is standard FPR cooling tower specification

Model

DTA

WY-10T

WY -20T

WY -30T

WY-40T

date

Runoff

m 3 /h

7.81

15.62

23.4

31.21

Air volume

CMM

85

160

230

280

Motor

KW

0.18

0.515

0.75

1.50

Noise (16m)

Dba

47

50

54

56.5

Suttle

Kg

46

67

116

130

Move weight

Kg

190

300

530

550

Pipe
Line

Water inlet

WI

50

63

80

80

Water outlet

WO

50

63

80

80

Over flow

OF

25

25

25

25

Tonnage

DR

25

25

25

25

Flow valve

FV

15

15

15

15

height

Tower

TH

1830

1930

1895

2040

Motor

MH

170

170

180

200

Casing

CH

1070

1140

1130

1255

Enterwind

AH

170

170

245

245

Water basin

WH

420

450

340

340

Water inlet

IH

270

280

175

175

Water outlet

OH

180

190

115

115

Ground work

FH

250

250

300

300

Diameter

Exhaust fan

ED

630

770

770

930

Water basin

WD

920

1165

1650

1650

Ground work

FD

520

730

1180

1180

Screw

CD

10×3

10×3

10×4

10×4

Dimension

Ground work

FS

250

250

300

300

Ground work

FC
       

L Plate L

PL

140

150

140

140

W Plate W

PW

120

140

150

150

C Plate C

PC
       

Screw

BC

450

635

835

835

Plate Center

SC

80

115

150

150

L Sock L

SL

390

515

780

780